Heat & Glo • PALOMA-BZ-MOD, PALOMA-GR-MOD, PALOMA-GY-MOD • 2189-900 Rev. i • 5/12
11. Place the wall thimble cover over the pipe assembly
and slide the appliance and vent assembly towards
the wall, carefully inserting the vent pipe into the vent
termination cap assembly. It is important that the vent
pipe extend into the vent termination cap a sufficient
distance so as to result in a minimum pipe overlap of
1-1/4 in. (32 mm). Secure the connection between the
vent pipe and the vent termination cap by attaching
the two sheet metal strips extending from the vent
termination cap assembly into the outer wall of the
vent pipe. Use the two sheet metal screws provided
to connect the strips to the pipe section (Figure 5.9).
Figure 5.9
WALL
THIMBLE
COVER
WALL THIMBLE
VINYL SIDING STANDOFF WITH
SIDING BENEATH REMOVED
SCREWS
BOLT HORIZONTAL TOP
TO VINYL STANDOFF
SCREWS
APPLY SEALANT TO
ALL FOUR SIDES
VINYL SIDING
Figure 5.8
Note: The attachment from the vent pipe to the vent
termination cap must be sealed with silicone. Termination
caps shall not be recessed into a wall or siding.
Fire Risk
Exhaust Fumes Risk
Impaired Performance of Appliance
Ensure vent components are locked
together correctly.
Pipe may separate if not properly joined.
WARNING
Do NOT connect a pipe section to a termination cap
without using the telescoping flue section found on the
termination cap.
WARNING
Burn Risk
Local codes may require installation of a
cap shield to prevent anything or anyone
from touching the hot cap.
WARNING
FOLD STRAP
HERE
WALL THIMBLE COVER/CEILING
FIRESTOP AS REQUIRED BY
LOCAL JURISDICTION
1/4 in. (6 mm)
STRAP
SHEET METAL
SCREW
WALL
THIMBLE